Type E Armoured Insulated Thermocouple Cable
Type E has the highest EMF output per degree of the common thermocouples, which helps where small temperature differences must be resolved or where signal runs are noisy. It is non-magnetic and is often used in power plant, cryogenic and test-bench work.
Armoured thermocouple cable adds a galvanised-steel or stainless-steel armour over the insulated pair or pairs, for direct burial, outdoor trays and areas with heavy mechanical risk. Multi-pair armoured cable is often used for long runs from field to control room.
Our Type E armoured cable uses Chromel (Ni-Cr) / Constantan (Cu-Ni) conductors in EX extension grade. Insulation per order (PVC, PTFE or fiberglass) with armour; rating set by the insulation. It follows the Violet (+) / White (−), violet sheath colour code under IEC 60584-3, with ANSI MC96.1 colours (Purple (+) / Red (−), purple sheath) available for export or imported instruments. Standard sizes are 7/36, 3/26, 3/28, 3/22, 1/24, 1/22, 0.5, 1, 1.5 and 2 sq mm, in single-pair or multi-pair construction.
Accuracy depends on using cable of the same type as the sensor and connecting it with the right polarity. A Type E sensor needs Type E extension or compensating cable all the way to the instrument; copper wire or cable of a different type adds an error wherever the junction is warm. Typical tolerance: EX Class 1 ±1.5°C, Class 2 ±2.5°C (IEC 60584-3).
When ordering Type E armoured cable, tell us the conductor size, number of pairs, total length, the colour standard your panel follows and the highest temperature the cable route will see. If only part of the route is hot, we can suggest a hot-zone section in a heat-resistant construction joined to a lower-cost cable for the cool run, which keeps accuracy while reducing cost.
Rewari Cable Industries manufactures this cable at our Rewari factory and supplies it in drums or cut lengths with a Material Test Certificate for each batch, covering conductor resistance, insulation resistance and spark test. Use the thermocouple cable configurator to pick size, insulation and length, or send your drawing on WhatsApp for a quote.
Specifications
| Thermocouple type | Type E |
|---|---|
| Conductor alloys | Chromel (Ni-Cr) / Constantan (Cu-Ni) |
| Grade | EX extension grade |
| Insulation system | Armoured |
| Temperature rating (cable) | Insulation per order (PVC, PTFE or fiberglass) with armour; rating set by the insulation |
| Sensor range (reference) | Sensor −200 to 900°C |
| Colour code IEC 60584-3 | Violet (+) / White (−), violet sheath |
| Colour code ANSI MC96.1 | Purple (+) / Red (−), purple sheath |
| Tolerance (typical) | EX Class 1 ±1.5°C, Class 2 ±2.5°C (IEC 60584-3) |
| Sizes | 7/36, 3/26, 3/28, 3/22, 1/24, 1/22, 0.5, 1, 1.5 and 2 sq mm |
| Construction | Single pair or multi-pair; drums or cut lengths |
| Documents | Batch Material Test Certificate (MTC) |
Typical values. Your TDS and batch MTC are the binding documents.
Typical applications
- Power plant auxiliary measurement
- Test benches and R&D rigs
- Low-temperature process lines
- Hot zones near furnace and boiler walls
Frequently asked questions
What is the colour code of Type E thermocouple cable?
Under IEC 60584-3 (used in India and Europe) it is Violet (+) / White (−), violet sheath. Under ANSI MC96.1 it is Purple (+) / Red (−), purple sheath. Tell us which standard your instruments follow.
Is armoured thermocouple cable available in multi-pair?
Yes. Tell us the number of pairs, insulation and armour type, and we will confirm the construction and outer diameter.
Can I use K-type or copper cable with a Type E sensor?
No. Only Type E extension or compensating cable keeps the reading correct. Other cable creates an error wherever its terminals are warmer than the instrument.
Do you supply a test certificate?
Yes. Every batch ships with a Material Test Certificate covering conductor resistance, insulation resistance and spark test.